GRW67P/S3A HY 30/24Li
Main Features
POWER SYSTEM
Type
HYBRID
FREQUENCY
Hz
50
VOLTAGE
V
400/230
Power Rating - Diesel Genset (According to standard ISO8528)
EMERGENCY STANDBY POWER ESP
kVA
66.0
EMERGENCY STANDBY POWER ESP
kW
52.8
PRIME POWER PRP
kVA
60.0
PRIME POWER PRP
kW
48.0
POWER FACTOR
cos ϕ
0.8
RATING DEFINITION (ACCORDING TO STANDARD ISO8528 1:2005)
Power Rating Hybrid Package
PEAK
kVA
PEAK
kW
MAX POWER
kVA
82.0
MAX POWER
kW
70.0
Engine specifications
ENGINE BRAND
Perkins
MODEL
1104D-44TG2
ENGINE COOLING SYSTEM
Water
EXHAUST EMISSION LEVEL
Stage IIIA
Alternator specifications
ALTERNATOR BRAND
LEROY SOMER
MODEL
LSA 42.3 L9
Dimensional data Canopy Version
INSTALLATION DRAWING CANOPY VERSION
INSTALLATION DRAWING CANOPY VERSION
INSTALLATION DRAWING CANOPY VERSION
112345
INSTALLATION DRAWING CANOPY VERSION